Engineering, 25.02.2020 22:30 khaz1430

A column in a building is subjected to the following load effects:

9 kips compression from dead load.
5 kips compression from roof live load.
6 kips compression from snow.
7 kips compression from.
3 inches of rain accumulated on the roof.
8 kips compression from wind

a. If load and resistance factor design is used, determine the factored load (required strength) to be used in the design of the column. Which AISC load combination controls?
b. What is the required design strength of the column?
c. What is the required nominal strength of the column for a resistance factor phi of 0.90?
d. If allowable strength design is used, determine the required load capacity (required strength) to be used in the design of the column. Which AISC load combination controls?
e. What is the required nominal strength of the column for a safety factor Ohm of 1.67?

ansver
Answers: 2

Another question on Engineering

question
Engineering, 04.07.2019 18:10
Which one from below is not one of the reasons of planning failures? (clo3) a)-planner is careless. b-planner spend less time in the field but more time on the desk c)-planner is not qualified d)-planner does not have sufficient time to properly plan
Answers: 3
question
Engineering, 04.07.2019 18:10
True or false (explain) (110)[111] is a slip system in bcc metals . the {111} family in fcc contains 8 planes. resolved shear stress (rss) in single crystals is just related to the applied stress. critical resolved shear stress (crss) in single crystal metals is direct proportional to the number of defects in the structure
Answers: 2
question
Engineering, 04.07.2019 18:10
Machinery that is a key part of the process and without which the plant or process cannot function is classifed as: (clo4) a)-critical machinery b)-essential machinery c)-general purpose machinery d)-none of the specified options.
Answers: 1
question
Engineering, 04.07.2019 18:20
What is the heat treatment of metals? what is the benefit of it? why and how it's useful? answer in details, do not write by hand.
Answers: 3
You know the right answer?
A column in a building is subjected to the following load effects:

9 kips compression f...
Questions
question
Mathematics, 05.11.2020 02:40
question
Mathematics, 05.11.2020 02:40
question
History, 05.11.2020 02:40
question
Advanced Placement (AP), 05.11.2020 02:40
Questions on the website: 13722361